Code-Checked 2×12 Stair Stringer Calculator
Solve exact unit rise, total horizontal run, framing-square layout marks, bottom heel tread drop, and stringer count with live residential building-code checks.
Calculate exact stair riser height, tread run, 2x12 stringer board length, bottom tread thickness drop, and residential IRC R311.7.5 code compliance with a notched 2D cut diagram.
Frequently Asked Questions
What is the maximum stair riser height and minimum tread depth under residential code?
Under International Residential Code (IRC R311.7.5), residential stair risers must not exceed 7-3/4 inches (7.75"), and tread depth measured horizontally nosing-to-nosing must be at least 10 inches (10.0"). Additionally, the largest riser height and smallest riser height within a flight cannot vary by more than 3/8 inch.
Why do you cut the bottom of a stair stringer shorter by the tread thickness?
Every step receives a finished tread (such as 1.5-inch thick 2×6 lumber) on top of the horizontal stringer cut. If you do not trim 1.5 inches ("drop the stringer") off the bottom heel of the stringer resting on the concrete landing pad, the bottom step becomes 1.5 inches taller than every other step and fails inspection.
What is the difference between a drop-riser mount and a flush-ledger stair mount?
In a standard drop-riser mount, the top of the stringer attaches one riser below the main deck surface so the deck itself acts as the top landing—meaning a flight with N risers has (N − 1) cut stringer treads. In a flush-ledger mount, the top stair tread sits flush with the deck surface, requiring N cut treads and a longer 2×12 board.
How many 2×12 stair stringers do I need for a 36-inch, 48-inch, or 60-inch wide deck stair?
Wood 2×6 treads are commonly supported on 16-inch maximum stringer centers (12-inch centers for composite stair treads). A 36-inch stair uses 3 stringers, a 48-inch stair uses 4 stringers, and a 60-inch stair uses 5 stringers—never leaving more than 5 inches of throat depth uncut on a #1 grade 2×12.
When is a stair handrail and concrete landing pad required?
Residential building codes require a continuous graspable handrail (34 to 38 inches vertically above stair nosings) on flights with 4 or more risers, plus a solid, level landing pad at least 36 inches deep by the full stair width at the bottom of exterior stairs.